Room Alert 26W Firmware v3.0.1 AvailableRoom Alert 26W Firmware v3.0.1 Released 23 June 2008
AVTECH Software is pleased to announce that an update to the Room Alert 26W Firmware is available for download at AVTECH.com.
NOTE: AVTECH Device Discovery v3.0.3 or higher is required for this update
***Please Read The Following Before Updating***
NOTE: AVTECH Device Discovery v3.0.3 or higher is required for this update. Please be sure any web browsers currently accessing the unit are closed to be sure all files are updated correctly.
IMPORTANT: This is a major firmware update. Please backup existing settings using AVTECH Device Discovery by right-clicking on the device in the list and selecting 'Backup Settings' before applying this update. Please carefully read all of the items below to review all new features and major updates.
Resolved an issue that could cause Digital Temperature Sensors to display a 32F reading when first connected.
Resolved an issue that could cause SNMP Traps to fail to be processed due to an invalid SysObjectID value.
Resolved an issue that could cause the value entered in the 'Adjust' field to change values due to incorrect rounding on sequential Sensor Settings saves.
Resolved an issue that could cause email messages to fail to send if the mail server replies with a long response to the EHLO command. We now check for a 250 response indicating it is 'OK' to send and discard the remaining unused message.
Resolved an issue that could cause email messages to fail to send if the mail server responded with an alternative error code to the EHLO command. We now correctly fall back to using HELO if the initial EHLO attempt fails and returns a code other than the 250 'OK' message.
Resolved an issue that could cause the humidity reading from a Digital Temp/Humidity Sensor connected to a WiSH Sensor to not be returned via SNMP.
Resolved an issue that could cause the internal temperature sensor on a WiSH Sensor to not properly trigger alarms when certain thresholds were set.
Added an option to display the time in the default 24 hour format or in 12 hour AM/PM format. This applies for the display on the Status screen as well as in email alert messages.
Added a status message when sensor labels are saved so a blank web page does not display before the 'Saving...' progress bar.
Added a new webpage display option designed specifically for mobile devices such as phones and PDAs that required a 'Content Type' to be passed with the page data. The new URL 'http://(IP of Device)/mobile.txt' will display a text only output of all current sensor data with a Content Type of 'text/plain'. The URL 'http://(IP of Device)/mobile' will still display a text only output of all sensor data without the Content Type header.
Added an 'Uptime' value to the '/getdata.htm' output for future use as a way to determine how long the device has been powered on.
Updated text displayed in the telnet menu to be more descriptive for some options and to resolve inaccuracies with others.