| Follow Us: Resellers|News|Company|
Computer Room, Server, Network, Temperature, Environment Monitoring & Alerting with Room Alert, TemPageR & Device ManageR! Computer Room, Server, Network, Temperature, Environment Monitoring & Alerting with Room Alert, TemPageR & Device ManageR!
AVTECH Support
Support Tickets
Submit Ticket
Lookup Ticket
Knowledge Base
FAQs
Application Notes
Technical Articles
Release Notes
Support Resources
Email-To-SMS Database
SNPP Database
TAP Dialup Database
Documentation
Device ManageR
AVTECH Device ManageR Advanced Software For Discovery, Management, Logging, Graphing, Alerting And More Logo The All-In-One Solution For Discovery, Management, Logging, Graphing, Alerting & More Of AVTECH's Environment Monitoring Hardware. Display Multiple Units Through A Single Web Interface, Set Up Multiple IP Addresses, View Multiple IP Cameras Across Your Network & More From Anywhere. Included With Room Alert & TemPageR.
FREE With Purchase! 
AVTECH Support

Product: Room Alert 32W/E
Article: Release Notes
Limit: 10
View All Room Alert 32W/E Release Notes View All Release Notes
September 30, 2011

Room Alert 32W Firmware v1.0.1 AvailableRoom Alert 32W Firmware v1.0.1 Released 30 September 2011

AVTECH Software is pleased to announce that an update to the Room Alert 32W Firmware is available for download at AVTECH.com.

***Please Read The Following Before Updating***

NOTE: AVTECH Device Discovery v3.1.1 or higher or AVTECH Device ManageR is required for this update. Please be sure any web browsers currently accessing the unit are closed to be sure all files are updated correctly.

  • Resolved an issue that could cause periodic false alarms for the internal Temp/Humidity Sensor. Because of heat generated inside the enclosure, the internal temperature sensor is automatically adjusted down by 7.5C. In some cases, the alarms were being checked prior to this adjust value being applied. This has been corrected so that alarms are only checked after the adjust value has been applied.
  • Resolved an issue that could cause some Heat Index thresholds to be checked against regular temperature thresholds. Some thresholds were also being interpreted in Celsius instead of Fahrenheit.
  • Added support for the additional relay output included on the Light Tower Adapter (LTA) for use with the Room Alert 32W.
  • Corrected a display issue with the title displayed on the Settings page.
  • For additional information about the updates included with Room Alert 32W v1.0.0 firmware, please click here.




Thank you for choosing Room Alert 26W and feel free to contact us at Support@AVTECH.com or 888.220.6700 if you have any questions.