Room Alert 32W Firmware v1.0.1 AvailableRoom Alert 32W Firmware v1.0.1 Released 30 September 2011
AVTECH Software is pleased to announce that an update to the Room Alert 32W Firmware is available for download at AVTECH.com.
***Please Read The Following Before Updating***
NOTE: AVTECH Device Discovery v3.1.1 or higher or AVTECH Device ManageR is required for this update. Please be sure any web browsers currently accessing the unit are closed to be sure all files are updated correctly.
Resolved an issue that could cause periodic false alarms for the internal Temp/Humidity Sensor. Because of heat generated inside the enclosure, the internal temperature sensor is automatically adjusted down by 7.5C. In some cases, the alarms were being checked prior to this adjust value being applied. This has been corrected so that alarms are only checked after the adjust value has been applied.
Resolved an issue that could cause some Heat Index thresholds to be checked against regular temperature thresholds. Some thresholds were also being interpreted in Celsius instead of Fahrenheit.
Added support for the additional relay output included on the Light Tower Adapter (LTA) for use with the Room Alert 32W.
Corrected a display issue with the title displayed on the Settings page.